Professional roof survey case study

ProImmune: roof condition survey and leak investigation report

Three commercial roofing and cladding surveys across Units 5, 9 and 10 at Oasis Park, followed by a detailed roof condition report, photographic evidence and prioritised recommendations.

Project
ProImmune, Oasis Park
Brief
Three roof and cladding condition surveys
Value
£3k+
Programme
Report issued 14 July 2026
ProImmune roof survey inspection evidence

ProImmune · Genuine inspection photographs from the completed survey report

01

Survey scope

TCR completed three non-invasive roofing and cladding condition surveys across Units 5, 9 and 10 at Oasis Park. The inspections covered the Café, Office and Plant Room roof areas and associated building-envelope interfaces.

02

Findings recorded

The report identified several issues contributing to water ingress, including missing or poorly reinstated curtain-wall pressure plates, deteriorated ridge foam fillers, inadequate historic GRP patch repairs, short ridge cappings, insufficient laps and sealant, missing roof fixings, open single-ply corner details and obstructed rainwater outlets.

03

Recommended actions

The recommendations included reinstating pressure plates, gaskets and seals, replacing missing fixings, removing inadequate patch repairs, improving vent and flashing details, replacing undersized ridge cappings and deteriorated fillers, repairing single-ply membrane defects and clearing obstructed outlets.

04

Value of the report

The completed report combined inspection photographs, defect descriptions, likely water-ingress routes and prioritised recommendations. It gave the client a clear basis for maintenance, repair and longer-term replacement decisions.

Your building

Need the condition of a roof explained before you commit to works?

Share the symptoms, access restrictions, photographs and decision you need the report to support. TCR will confirm whether a professional survey, leak investigation or specification review is the correct next step.